Skip to content
BITMAIN
ANTSPACE HW5 — image 1 of 3
ANTSPACE

SPOTANTSPACE HW5

Function
BTC/BCH/BSV SHA256
Specifications
1Set | 1200kW | 210 Rack Space
Cooling
Hydro-Cooling
Weight
16000 kg
Price
$84,000
Shipping Date
Shipping in 60 working days after fully paid

For orders of 100 units or more, use Bulk Order.

| Specifications


Product Overview Value
Model ANTSPACE HW5
Version V1
Dimensions (l*w*h), mm 12192×2438×2896
Miner capacity 210 units  S23 Hyd. & S21 Hyd. & S19 Hyd. Series miner

PUE@25℃ ambient temperature

1.017

Container certification CSC
Safety certification NFPA 79:2021
UL 508A:2018 R8.21
CSA C22.2 No. 14-18
ANSI/ISO 12100:2012
IEC 60204 Ed 5.1 2009
Input voltage and frequency 400V±5% 50/60Hz
Detailed Characteristics Value
Shipping weight, T 14
Operating weight, T 24
Main switch of power distribution cabinets, A 1200*2
Rated current, A ≤986*2
Rated Current per Miner, A ≤10
Normal power, kW 1200
Inlet cable(1-1) The inlet copper cables can withstand voltage of above 600V, with the following requirements:
L1 single core cable 600kcMil(300mm²)x6
L2 single core cable 600kcMil(300mm²)x6
L3 single core cable 600kcMil(300mm²)x6
N Single-core cable 600kcMil(300mm²)x4
PE single-core cable 500kcMil(240mm²)x2
Flow rate, m³/h ≥85
Quantity of ANTSPACE powered by one 2500kVA Transformer 2
ANTSPACE HW5 Dry-Wet Tower Cooling Module  
Heat Dissipation Capacity, kW 1200
Outlet Temperature @ 28℃ Wet Bulb Temperature, ˚C 35
Operating Power, kW ≤15~29
Water supply pipe Interface DN40(Internal thread)
Drain Pipe Interface DN65(Internal thread)
Noise level @25℃, 15m, dBA 70
Water Consumption, m³/h 0.7~1.3
Inner Coolant Usage, m³ 1.6

Notes:  

(1) For aluminum cables, refer to electrical specifications and use copper-aluminum composite terminals that meet standard requirements.