Skip to content
BITMAIN
AR1904 — image 1 of 6
ANTMINER

SPOTAR1904

Function
BTC/BCH/BSV SHA256
Specifications
1028TW | 32kW | 4 S19 XP Hyd. and Rack | 80℃ Heating Capacity
Cooling
Hydro-Cooling
Weight
494.2 kg
Price
$9,916
Shipping Date
Shipping in 20 working days after fully paid

For orders of 100 units or more, use Bulk Order.

| Specifications for AR1904


Product Glance Value
Model ANTRACK
Version AR22
Capacity 4 units ANTMINER (Hydro) or
2 units ANTMINER (U2 Hydro) or
2 units ANTMINER (U3 Hydro) 
Miner maximum load,kW 24
Total load,kW 32
Detailed Characteristics Value
Part 1: Mining Cabinet  
Hardware Configuration  

Size (Length*Width*Height), mm (without package)

1200*600*1200

Size (Length*Width*Height), mm (with package)

1460*780*1330

Net weight, kg (without package)

132

Gross weight, kg (with package)

193

Network connection mode

RJ45 Ethernet 10/100M

Power Supply  
Power supply AC Input voltage, Volt(1-1) 380~415V AC
Power supply AC Input Frequency Range, Hz 50~60
Power supply AC Input current, Amp(1-2) 63
Water pump  

Rated power, W

450

Noise, dBA@1m

60
Lift, m 19
Size (Length*Width* Height), mm 360*210*268
Plate heat exchanger  
Maximum heat exchange power, kW 30
Size (Length*Width*Height), mm  305*106*64
Diameter of water pipe connector, mm  DN20
Part 2: External Cooler(1-3)  
Hardware Configuration  
Size (Length*Width*Height), mm (without package)

1370*555*1333

Size (Length*Width*Height), mm (with package)

1500*610*1880

Net weight, kg (without package)

225

Gross weight, kg (with package)

263

Power supply  
Power supply AC input voltage, Volt(1-1) 380~415V AC
Power supply AC input frequency range, Hz 50~60
Maximum power supply AC input current, Amp(1-2) 21
Heat pump  
Heating Capacity(typical), kW 32
Compressor Input(typical), kW 8
EER(typical) 3.0
Sound Level, dB(A) 50
Refrigerant R290
Heating water outlet temperature, °C 80
Fan  
Rated power, W 500
Noise, dBA@1m 50
Size (Length*Height*Thickness), mm 551*551*160
Water pump  
Rated power, W 180
Noise, dBA@1m 30
Size (Length*Widht*Height), mm 130*551*129
Environment Requirements  
Ambient temperature, °C -20~40
Water flow, L/min 32.0~40.0(Cabinet side)
Water flow, L/min 32.0~40.0(Heating side)
Water pressure, bar ≤3.5
Working fluid(1-4) Organic Antifreeze (10%)
Installation distance, m(1-5) 5
Liquid PH 7.8~8.5
Storage temperature, °C -20~70
Operation humidity(non-condensing), RH 10~90%

Notes:

(1-1) Caution: Wrong input voltage may probably cause miner damaged.

(1-2) Three-phase AC input.

(1-3) The External cooler (heat pump) should be placed outdoors in a well-ventilated environment.

(1-4) If the water conductivity is ≥100 μs/cm, the fluid must be replaced. The water conductivity is less than 20 μs/cm when the system is running at the first time.

(1-5) The distance between mining cabinet and external cooler.

| Specification Details For S19 XP Hyd.


Product Glance  
Model S19 XP Hyd.
Version 10
Crypto algorithm/coins SHA256 | BTC/BCH/BSV
Typical hashrate, TH/s(1-1) 257
Power on wall @35°C(1-2), Watt(1-1) 5,346
Power efficiency on wall @35°C(1-2), J/TH(1-1) 20.8
Detailed Characteristics  
Power Supply  
Phase 3
Input voltage, Volt(2-1) 380~415
Input Frequency Range, Hz 50~60
Input max current, Amp 12
Hardware Configuration  
Networking connection mode RJ45 Ethernet 10/100M
Server Size (Length*Width*Height, w/o package), mm 410*170*209
Server Size (Length*Width*Height, with package), mm 570*316*430
Net weight, kg(2-2) 12.8
Gross weight, kg 14.1
Environment Requirements  

Inlet coolant temperature,°C

20~40

Coolant flow, L/min

8.0~10.0

Coolant pressure, bar

≤3.5

Working coolant(2-2)

Antifreeze/ Pure water/Deionized water

Coolant pH value

Antifreeze: 7.0~9.0

Prue water: 6.5~7.5

Deionized water:8.5~9.5

Diameter of coolant pipe connector, mm

OD10
Storage temperature,°C -20~70
Operation humidity(non-condensing) , RH 10~90%

NOTE:

(1-1) The hashrate value, power on wall, and power efficiency on wall are all typical values.The actual hashrate value fluctuates by ± 3%, and the actual power on wall and powerefficiency on wall fluctuate by ±5%.
(1-2) Inlet coolant temperature.
(2-1) Caution: Wrong input voltage may cause server damaged.
(2-2) For detailed working coolant use and maintenance instructions, please refer to "ANTSPACE HW7 Liquid cooling container & Dry-cooling Tower product manual", Chapter 9, Article 3, Point 6, "Coolant Maintenance"!

PS: Please note that the Hydro-cooling miners are shipped without power cables. There are power cables inside the ANTRACK.