Skip to content
BITMAIN
ANTSPACE HW7 — image 1 of 5
ANTSPACE

SPOTANTSPACE HW7

Function
BTC/BCH/BSV SHA256
Specifications
1Set | 2000kW | 242 2U-type (S23e U2H) miners or 396 T-type miners
Cooling
Hydro-Cooling
Weight
27600 kg
Price
$169,000
Shipping Date
Shipping in 60 working days after fully paid

For orders of 100 units or more, use Bulk Order.

| Specifications


Product Overview Value
Model ANTSPACE HW7
Dimensions (L*W*H), mm 12192*2438*2896
Miner Capacity

242 2U-type (S23e U2H) miners or 396 T-type miners

PUE

1.03 @ 25℃ ambient temperature, 35℃ supply liquid temperature

Supply-to-ambient temperature, ℃ ≤5
Container certification Classification Society Certification
Safety Certification NFPA 79:2024
UL 508A:2018 R7.22
CSA C22.2 No. 301:23
UL 2011:2022
UL 2755:2018
EN 60204-1:2018
EN ISO 12100:2010
Certifications Complete machine Notrth America, CE certicifation
Input Voltage, V 380~480 (50/60Hz, 3P/N/PE)
Ambient Temperature, ℃ -40~50
Ambient Humidity, RH 10%~90%
Altitude, m ≤2000
Product life 10 years
Detailed Specifications Value
Shipping weight, T 16
Operating weight, T 25
Main Switch Capacity of Power Distribution Cabinet, A 1200
Rated Power, kW 2100
Maximum Supported Input Current, A 960*4
Maximum Supported Input Power, kW 2500
Maximum Current per Miner Slot, A 25
Inlet cable The inlet cables can withstand high voltage above 600V. Single-phase requirements are as follows:
Copper cables:
L1 cable 600kcmil *12
L2 cable 600kcmil *12
L3 cable 600kcmil *12
N cable 600kcmil *8
PE cable 600kcmil *4
Aluminum cables:
L1 cable 800kcmil *12
L2 cable 800kcmil *12
L3 cable 800kcmil *12
N cable 800kcmil *8
PE cable 800kcmil *4
External Interface Tri-Clamp Interface: DN125 ISO 139.7 (ISO2852)
Flow rate, m³/h <117*2
Rated Power of Circulation Pump, kW 30*2
Cooling Unit Specifications
Product Overview Value
Type Dry Cooler + Water Curtain
Quantity 1
Dry Cooler Dimensions (L*W*H), mm 12192*2438*2896
Water Curtain Dimensions (L*W*T), mm 11700*2250*150 (single side)
Heat Dissipation Capacity, kW 2000
Supply Liquid Temperature, ℃ 35±1℃ @ 30℃ ambient
49±1℃ @ 50℃ ambient
(with cooling pad enabled)
Container Certification Classification Society Certification
Rated Power of Cooling Fan, kW 4.1*22
Rated Power of Water Curtain Pump, kW 1.5*2
Input Voltage, V 380~480 (50/60Hz, 3P/N/PE)
Detailed Specifications Value
Shipping Weight, T 14
Operating Weight, T 16
Connection Interface Tri-Clamp Interface: DN125 ISO 139.7 (ISO2852)
Noise Level (25℃, 15m), dBA 75
Pipe Material 304 Stainless Steel
Cooling pad Water Consumption, m³/h 0.25~5.3
Coolant Usage, m³ 3.2